Description
The W22Xec motor offer safety and reliability for operation in a great variety of applications that require a non-incendive motor (Zone 2). It provides safety and complies with efficiency level specified by IEC 60034-30-1. It meets the requirements of installations where the flammable mixture is not often present, but may present risks.
Standard | IEC 60034-1 |
---|---|
Frequency | 50 Hz |
Voltage | 380-400-415/660-690//460 V |
Number of poles | 6 |
Degree of Protection | IP55 |
Synchronous speed | 1000 rpm |
Output rating | 250 kW |
Mounting | B3T |
Flange | Without |
Terminal box¹ | Top |
Enclosure | IC411 - TEFC |
Electric Motors
Frame | 355M/L |
---|---|
Output | 250 kW (340 HP) |
Number of Poles | 6 |
Frequency | 50 Hz |
Rated speed | 992 rpm |
Slip | 0.80 % |
Rated voltage | 380/660 V |
Rated current | 496/286 A |
L. R. Amperes | 2827/1628 A |
LRC | 5.7 |
No load current | 170/97.9 A |
Rated torque | 1780 ft.lb |
Locked rotor torque | 190 % |
Breakdown torque | 200 % |
Locked rotor time | 77s (cold) 43s (hot) |
Moment of inertia (J) | 329 sq.ft.lb |
Design | N |
Insulation Class | F |
Service factor | 1.00 |
Temperature rise | 80 K |
Duty Cycle | S1 |
Starting Method | Direct On Line |
Ambient temperature | -20°C to +40°C |
Altitude | 1000 m.a.s.l. |
Degree of Protection | IP55 |
Enclosure | IC411 - TEFC |
Mounting | B3T |
Rotation¹ | Both (CW and CCW) |
Noise level² | 73.0 dB(A) |
Approx. weight³ | 4035 lb |
Efficiency
50% | 95.0 |
---|---|
75% | 95.5 |
100% | 95.8 |
Power factor
50% | 0.68 |
---|---|
75% | 0.77 |
100% | 0.80 |
Electric Motors
Frame | 355M/L |
---|---|
Output | 250 kW (340 HP) |
Number of Poles | 6 |
Frequency | 50 Hz |
Rated speed | 993 rpm |
Slip | 0.70 % |
Rated voltage | 400/690 V |
Rated current | 477/277 A |
L. R. Amperes | 3053/1770 A |
LRC | 6.4 |
No load current | 185/107 A |
Rated torque | 1770 ft.lb |
Locked rotor torque | 210 % |
Breakdown torque | 220 % |
Locked rotor time | 68s (cold) 38s (hot) |
Moment of inertia (J) | 329 sq.ft.lb |
Design | N |
Insulation Class | F |
Service factor | 1.00 |
Temperature rise | 80 K |
Duty Cycle | S1 |
Starting Method | Direct On Line |
Ambient temperature | -20°C to +40°C |
Altitude | 1000 m.a.s.l. |
Degree of Protection | IP55 |
Enclosure | IC411 - TEFC |
Mounting | B3T |
Rotation¹ | Both (CW and CCW) |
Noise level² | 73.0 dB(A) |
Approx. weight³ | 4035 lb |
Efficiency
50% | 95.0 |
---|---|
75% | 95.5 |
100% | 95.8 |
Power factor
50% | 0.64 |
---|---|
75% | 0.75 |
100% | 0.79 |
Electric Motors
Frame | 355M/L |
---|---|
Output | 250 kW (340 HP) |
Number of Poles | 6 |
Frequency | 50 Hz |
Rated speed | 994 rpm |
Slip | 0.60 % |
Rated voltage | 415 V |
Rated current | 465 A |
L. R. Amperes | 3209 A |
LRC | 6.9 |
No load current | 195 A |
Rated torque | 1770 ft.lb |
Locked rotor torque | 229 % |
Breakdown torque | 240 % |
Locked rotor time | 63s (cold) 35s (hot) |
Moment of inertia (J) | 329 sq.ft.lb |
Design | N |
Insulation Class | F |
Service factor | 1.00 |
Temperature rise | 80 K |
Duty Cycle | S1 |
Starting Method | Direct On Line |
Ambient temperature | -20°C to +40°C |
Altitude | 1000 m.a.s.l. |
Degree of Protection | IP55 |
Enclosure | IC411 - TEFC |
Mounting | B3T |
Rotation¹ | Both (CW and CCW) |
Noise level² | 73.0 dB(A) |
Approx. weight³ | 4035 lb |
Efficiency
50% | 95.0 |
---|---|
75% | 95.5 |
100% | 95.8 |
Power factor
50% | 0.61 |
---|---|
75% | 0.73 |
100% | 0.78 |
Electric Motors
Frame | 355M/L |
---|---|
Output | 250 kW (340 HP) |
Number of Poles | 6 |
Frequency | 60 Hz |
Rated speed | 1194 rpm |
Slip | 0.50 % |
Rated voltage | 460 V |
Rated current | 420 A |
L. R. Amperes | 3066 A |
LRC | 7.3 |
No load current | 175 A |
Rated torque | 1480 ft.lb |
Locked rotor torque | 229 % |
Breakdown torque | 240 % |
Locked rotor time | 73s (cold) 41s (hot) |
Moment of inertia (J) | 329 sq.ft.lb |
Design | N |
Insulation Class | F |
Service factor | 1.00 |
Temperature rise | 80 K |
Duty Cycle | S1 |
Starting Method | Direct On Line |
Ambient temperature | -20°C to +40°C |
Altitude | 1000 m.a.s.l. |
Degree of Protection | IP55 |
Enclosure | IC411 - TEFC |
Mounting | B3T |
Rotation¹ | Both (CW and CCW) |
Noise level² | 77.0 dB(A) |
Approx. weight³ | 4035 lb |
Efficiency
50% | 95.0 |
---|---|
75% | 95.5 |
100% | 95.8 |
Power factor
50% | 0.62 |
---|---|
75% | 0.73 |
100% | 0.78 |
Features
Frame Material | Cast Iron |
---|---|
Impregnation Method | Constant Resin Flow |
Regreasing System | At Drive end and Non-drive end |
Main terminal box hole | 2xM63x1,5 |
Terminal Block | BMC - 6 pins |
Shaft Locking Device | Without |
Drain | Rubber, automatic |
Shaft Material | SAE 4140 Carbon Steel |
Painting | RAL 5009 205P (ISO 12944 - C3) |
Grounding Lugs | Double |
Fan Cover material | Cast Iron |
Tropicalized Painting | Without |
Fan material | Aluminum |
Bearing cap | Yes- Bearing Cap |
Winding thermal protection | Thermistor - 2 wires 1 per phase 140°C Thermistor - 2 wires 1 per phase 155°C |
Balancing Method | 1/2 Key |
Drip Cover | Without |
Overload protector (phenolic) | Without overload protector |
Connection Cables Quantity | 6 |