The W22Xec motor offer safety and reliability for operation in a great variety of applications that require a non-incendive motor (Zone 2). It provides safety and complies with efficiency level specified by IEC 60034-30-1. It meets the requirements of installations where the flammable mixture is not often present, but may present risks.

Standard IEC 60034-1
Frequency 50 Hz
Voltage 380-400-415/660-690//460 V
Number of poles 4
Degree of Protection IP55
Synchronous speed 1500 rpm
Output rating 200 kW
Mounting B3T
Flange Without
Terminal box¹ Top
Enclosure IC411 - TEFC


Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 4
Frequency 50 Hz
Rated speed 1490 rpm
Slip 0.67 %
Rated voltage 380/660 V
Rated current 367/211 A
L. R. Amperes 2202/1268 A
LRC 6.0
No load current 105/60.5 A
Rated torque 946 ft.lb
Locked rotor torque 200 %
Breakdown torque 220 %
Locked rotor time 39s (cold) 22s (hot)
Moment of inertia (J) 166 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 76.0 dB(A)
Approx. weight³ 3297 lb
Efficiency
50% 95.8
75% 96.0
100% 96.2
Power factor
50% 0.75
75% 0.83
100% 0.86
Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 4
Frequency 50 Hz
Rated speed 1491 rpm
Slip 0.60 %
Rated voltage 400/690 V
Rated current 353/205 A
L. R. Amperes 2295/1330 A
LRC 6.5
No load current 115/66.7 A
Rated torque 945 ft.lb
Locked rotor torque 210 %
Breakdown torque 240 %
Locked rotor time 39s (cold) 22s (hot)
Moment of inertia (J) 166 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 76.0 dB(A)
Approx. weight³ 3297 lb
Efficiency
50% 95.8
75% 96.0
100% 96.2
Power factor
50% 0.72
75% 0.81
100% 0.85
Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 4
Frequency 50 Hz
Rated speed 1492 rpm
Slip 0.53 %
Rated voltage 415 V
Rated current 344 A
L. R. Amperes 2408 A
LRC 7.0
No load current 125 A
Rated torque 945 ft.lb
Locked rotor torque 229 %
Breakdown torque 260 %
Locked rotor time 39s (cold) 22s (hot)
Moment of inertia (J) 166 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 76.0 dB(A)
Approx. weight³ 3297 lb
Efficiency
50% 95.8
75% 96.2
100% 96.3
Power factor
50% 0.69
75% 0.79
100% 0.84
Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 4
Frequency 60 Hz
Rated speed 1792 rpm
Slip 0.44 %
Rated voltage 460 V
Rated current 311 A
L. R. Amperes 2333 A
LRC 7.5
No load current 110 A
Rated torque 787 ft.lb
Locked rotor torque 260 %
Breakdown torque 280 %
Locked rotor time 84s (cold) 47s (hot)
Moment of inertia (J) 166 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 81.0 dB(A)
Approx. weight³ 3297 lb
Efficiency
50% 95.0
75% 95.8
100% 96.2
Power factor
50% 0.71
75% 0.80
100% 0.84
Features
Frame Material Cast Iron
Impregnation Method Constant Resin Flow
Regreasing System At Drive end and Non-drive end
Main terminal box hole 2xM63x1,5
Terminal Block BMC - 6 pins
Shaft Locking Device Without
Drain Rubber, automatic
Shaft Material SAE 4140 Carbon Steel
Painting RAL 5009 205P (ISO 12944 - C3)
Grounding Lugs Double
Fan Cover material Cast Iron
Tropicalized Painting Without
Fan material Aluminum
Bearing cap Yes- Bearing Cap
Winding thermal protection Thermistor - 2 wires 1 per phase 140°C Thermistor - 2 wires 1 per phase 155°C
Balancing Method 1/2 Key
Drip Cover Without
Overload protector (phenolic) Without overload protector
Connection Cables Quantity 6