WEG E20012ET3YAX355MLF3W W22Xec IE3 200 kW 6P 355M/L 3Ph 380-400-415/660-690//460 V 50 Hz IC411 - TEFC - B3T

WEGSKU: E20012ET3YAX355MLF3W

Drop-Ship

Price:
Sale price$75,302.15

Description

The W22Xec motor offer safety and reliability for operation in a great variety of applications that require a non-incendive motor (Zone 2). It provides safety and complies with efficiency level specified by IEC 60034-30-1. It meets the requirements of installations where the flammable mixture is not often present, but may present risks.

Standard IEC 60034-1
Frequency 50 Hz
Voltage 380-400-415/660-690//460 V
Number of poles 6
Degree of Protection IP55
Synchronous speed 1000 rpm
Output rating 200 kW
Mounting B3T
Flange Without
Terminal box¹ Top
Enclosure IC411 - TEFC


Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 992 rpm
Slip 0.80 %
Rated voltage 380/660 V
Rated current 387/223 A
L. R. Amperes 2129/1226 A
LRC 5.5
No load current 140/80.6 A
Rated torque 1420 ft.lb
Locked rotor torque 170 %
Breakdown torque 190 %
Locked rotor time 79s (cold) 44s (hot)
Moment of inertia (J) 247 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 73.0 dB(A)
Approx. weight³ 3572 lb
Efficiency
50% 95.7
75% 96.0
100% 95.8
Power factor
50% 0.70
75% 0.79
100% 0.82
Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 993 rpm
Slip 0.70 %
Rated voltage 400/690 V
Rated current 376/218 A
L. R. Amperes 2294/1330 A
LRC 6.1
No load current 150/87.0 A
Rated torque 1420 ft.lb
Locked rotor torque 190 %
Breakdown torque 210 %
Locked rotor time 70s (cold) 39s (hot)
Moment of inertia (J) 247 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 73.0 dB(A)
Approx. weight³ 3572 lb
Efficiency
50% 95.5
75% 96.0
100% 95.9
Power factor
50% 0.66
75% 0.76
100% 0.80
Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 993 rpm
Slip 0.70 %
Rated voltage 415 V
Rated current 367 A
L. R. Amperes 2422 A
LRC 6.6
No load current 160 A
Rated torque 1420 ft.lb
Locked rotor torque 210 %
Breakdown torque 229 %
Locked rotor time 64s (cold) 36s (hot)
Moment of inertia (J) 247 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 73.0 dB(A)
Approx. weight³ 3572 lb
Efficiency
50% 95.3
75% 95.9
100% 95.9
Power factor
50% 0.63
75% 0.74
100% 0.79
Electric Motors
Frame 355M/L
Output 200 kW (270 HP)
Number of Poles 6
Frequency 60 Hz
Rated speed 1194 rpm
Slip 0.50 %
Rated voltage 460 V
Rated current 328 A
L. R. Amperes 2296 A
LRC 7.0
No load current 140 A
Rated torque 1180 ft.lb
Locked rotor torque 210 %
Breakdown torque 240 %
Locked rotor time 79s (cold) 44s (hot)
Moment of inertia (J) 247 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 77.0 dB(A)
Approx. weight³ 3572 lb
Efficiency
50% 95.0
75% 95.8
100% 95.8
Power factor
50% 0.64
75% 0.75
100% 0.80
Features
Frame Material Cast Iron
Impregnation Method Constant Resin Flow
Regreasing System At Drive end and Non-drive end
Main terminal box hole 2xM63x1,5
Terminal Block BMC - 6 pins
Shaft Locking Device Without
Drain Rubber, automatic
Shaft Material SAE 4140 Carbon Steel
Painting RAL 5009 205P (ISO 12944 - C3)
Grounding Lugs Double
Fan Cover material Cast Iron
Tropicalized Painting Without
Fan material Aluminum
Bearing cap Yes- Bearing Cap
Winding thermal protection Thermistor - 2 wires 1 per phase 140°C Thermistor - 2 wires 1 per phase 155°C
Balancing Method 1/2 Key
Drip Cover Without
Overload protector (phenolic) Without overload protector
Connection Cables Quantity 6
Downloads

You may also like

Recently viewed