WEG E11012ET3YAX315SMF3W W22Xec IE3 110 kW 6P 315S/M 3Ph 380-400-415/660-690//460 V 50 Hz IC411 - TEFC - B3T

WEGSKU: E11012ET3YAX315SMF3W

GTIN :

MPN :

Dropship

Price:
Sale price$45,413.00

Description

The W22Xec motor offer safety and reliability for operation in a great variety of applications that require a non-incendive motor (Zone 2). It provides safety and complies with efficiency level specified by IEC 60034-30-1. It meets the requirements of installations where the flammable mixture is not often present, but may present risks.

Standard IEC 60034-1
Frequency 50 Hz
Voltage 380-400-415/660-690//460 V
Number of poles 6
Degree of Protection IP55
Synchronous speed 1000 rpm
Output rating 110 kW
Mounting B3T
Flange Without
Terminal box¹ Top
Enclosure IC411 - TEFC


Electric Motors
Frame 315S/M
Output 110 kW (150 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 990 rpm
Slip 1.00 %
Rated voltage 380/660 V
Rated current 217/125 A
L. R. Amperes 1302/750 A
LRC 6.0
No load current 93.0/53.5 A
Rated torque 783 ft.lb
Locked rotor torque 200 %
Breakdown torque 240 %
Locked rotor time 48s (cold) 27s (hot)
Moment of inertia (J) 146 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 67.0 dB(A)
Approx. weight³ 2293 lb
Efficiency
50% 94.8
75% 95.0
100% 95.1
Power factor
50% 0.66
75% 0.76
100% 0.81
Electric Motors
Frame 315S/M
Output 110 kW (150 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 991 rpm
Slip 0.90 %
Rated voltage 400/690 V
Rated current 211/122 A
L. R. Amperes 1372/795 A
LRC 6.5
No load current 104/60.3 A
Rated torque 782 ft.lb
Locked rotor torque 229 %
Breakdown torque 270 %
Locked rotor time 43s (cold) 24s (hot)
Moment of inertia (J) 146 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 67.0 dB(A)
Approx. weight³ 2293 lb
Efficiency
50% 94.0
75% 94.8
100% 95.1
Power factor
50% 0.61
75% 0.74
100% 0.79
Electric Motors
Frame 315S/M
Output 110 kW (150 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 992 rpm
Slip 0.80 %
Rated voltage 415 V
Rated current 209 A
L. R. Amperes 1463 A
LRC 7.0
No load current 115 A
Rated torque 782 ft.lb
Locked rotor torque 250 %
Breakdown torque 300 %
Locked rotor time 37s (cold) 21s (hot)
Moment of inertia (J) 146 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 67.0 dB(A)
Approx. weight³ 2293 lb
Efficiency
50% 93.0
75% 94.5
100% 95.1
Power factor
50% 0.57
75% 0.70
100% 0.77
Electric Motors
Frame 315S/M
Output 110 kW (150 HP)
Number of Poles 6
Frequency 60 Hz
Rated speed 1193 rpm
Slip 0.58 %
Rated voltage 460 V
Rated current 185 A
L. R. Amperes 1332 A
LRC 7.2
No load current 94.0 A
Rated torque 650 ft.lb
Locked rotor torque 250 %
Breakdown torque 300 %
Locked rotor time 55s (cold) 31s (hot)
Moment of inertia (J) 146 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 70.0 dB(A)
Approx. weight³ 2293 lb
Efficiency
50% 94.0
75% 95.6
100% 95.8
Power factor
50% 0.60
75% 0.71
100% 0.78
Features
Frame Material Cast Iron
Impregnation Method Constant Resin Flow
Regreasing System At Drive end and Non-drive end
Main terminal box hole 2xM63x1,5
Terminal Block BMC - 6 pins
Shaft Locking Device Without
Drain Rubber, automatic
Shaft Material SAE 1040/45 Carbon Steel
Painting RAL 5009 205P (ISO 12944 - C3)
Grounding Lugs Double
Fan Cover material Cast Iron
Tropicalized Painting Without
Fan material Conductive Plastic
Bearing cap Yes- Bearing Cap
Winding thermal protection Thermistor - 2 wires 1 per phase 140°C Thermistor - 2 wires 1 per phase 155°C
Balancing Method 1/2 Key
Drip Cover Without
Overload protector (phenolic) Without overload protector
Connection Cables Quantity 6
Downloads

You may also like

Recently viewed