WEG E01812XP3YAX200LF3-W W22Xdb IE2 18.5 kW 6P 200M/L 3Ph 380-400-415/660-690//460 V 50 Hz IC411 - TEFC - B3T

WEGSKU: E01812XP3YAX200LF3-W

Drop-Ship

Price:
Sale price$6,451.83

Description

The W22Xdb line is an evolution in the market of classified area products offering high efficiency levels, energy saving, low operational costs, extended lifetime, low maintenance and assured safety.

Standard IEC 60034-1
Frequency 50 Hz
Voltage 380-400-415/660-690//460 V
Number of poles 6
Degree of Protection IP56
Synchronous speed 1000 rpm
Output rating 18.5 kW
Mounting B3T
Flange Without
Terminal box¹ Top
Enclosure IC411 - TEFC


Electric Motors
Frame 200M/L
Output 18.5 kW (25 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 970 rpm
Slip 3.00 %
Rated voltage 380/660 V
Rated current 36.9/21.2 A
L. R. Amperes 210/121 A
LRC 5.7
No load current 13.5/7.77 A
Rated torque 134 ft.lb
Locked rotor torque 190 %
Breakdown torque 220 %
Locked rotor time 27s (cold) 15s (hot)
Moment of inertia (J) 8.34 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 60.0 dB(A)
Approx. weight³ 677 lb
Efficiency
50% 91.5
75% 91.4
100% 90.8
Power factor
50% 0.71
75% 0.80
100% 0.84
Electric Motors
Frame 200M/L
Output 18.5 kW (25 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 975 rpm
Slip 2.50 %
Rated voltage 400/690 V
Rated current 35.7/20.7 A
L. R. Amperes 203/118 A
LRC 5.7
No load current 15.0/8.70 A
Rated torque 134 ft.lb
Locked rotor torque 210 %
Breakdown torque 250 %
Locked rotor time 27s (cold) 15s (hot)
Moment of inertia (J) 8.34 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 60.0 dB(A)
Approx. weight³ 677 lb
Efficiency
50% 91.0
75% 91.4
100% 91.2
Power factor
50% 0.67
75% 0.77
100% 0.82
Electric Motors
Frame 200M/L
Output 18.5 kW (25 HP)
Number of Poles 6
Frequency 50 Hz
Rated speed 975 rpm
Slip 2.50 %
Rated voltage 415 V
Rated current 35.2 A
L. R. Amperes 201 A
LRC 5.7
No load current 16.3 A
Rated torque 134 ft.lb
Locked rotor torque 229 %
Breakdown torque 270 %
Locked rotor time 27s (cold) 15s (hot)
Moment of inertia (J) 8.34 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 60.0 dB(A)
Approx. weight³ 677 lb
Efficiency
50% 90.5
75% 91.2
100% 91.3
Power factor
50% 0.63
75% 0.74
100% 0.80
Electric Motors
Frame 200M/L
Output 18.5 kW (25 HP)
Number of Poles 6
Frequency 60 Hz
Rated speed 1175 rpm
Slip 2.08 %
Rated voltage 460 V
Rated current 31.3 A
L. R. Amperes 200 A
LRC 6.4
No load current 13.7 A
Rated torque 111 ft.lb
Locked rotor torque 250 %
Breakdown torque 280 %
Locked rotor time 27s (cold) 15s (hot)
Moment of inertia (J) 8.34 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 62.0 dB(A)
Approx. weight³ 677 lb
Efficiency
50% 91.0
75% 91.7
100% 91.7
Power factor
50% 0.64
75% 0.76
100% 0.81
Features
Frame Material Cast Iron
Impregnation Method Dip and Bake Polyester
Regreasing System At Drive end and Non-drive end
Space Heater Voltage 200 - 240 V
Main terminal box hole 2xM50x1,5
Terminal Block BMC - 6 pins
Shaft Locking Device Without
Shaft Material SAE 1040/45 Carbon Steel
Painting RAL 5009 205P (ISO 12944 - C4)
Grounding Lugs Double
Fan Cover material Cast Iron
Tropicalized Painting Without
Joints Seal Lumomoly
Fan material Aluminum
Bearing cap Yes- Bearing Cap
Bolt Material Carbon Steel
Winding thermal protection Thermistor - 2 wires 1 per phase 150°C
Drip Cover Without
Overload protector (phenolic) Without overload protector
Connection Cables Quantity 6
Downloads