WEG E01118XP3YAX160MF3-W W22Xdb IE2 11 kW 4P 160M/L 3Ph 380-400-415/660-690//460 V 50 Hz IC411 - TEFC - B3T

WEGSKU: E01118XP3YAX160MF3-W

Drop-Ship

Price:
Sale price$3,196.28

Description

The W22Xdb line is an evolution in the market of classified area products offering high efficiency levels, energy saving, low operational costs, extended lifetime, low maintenance and assured safety.

Standard IEC 60034-1
Frequency 50 Hz
Voltage 380-400-415/660-690//460 V
Number of poles 4
Degree of Protection IP56
Synchronous speed 1500 rpm
Output rating 11 kW
Mounting B3T
Flange Without
Terminal box¹ Top
Enclosure IC411 - TEFC


Electric Motors
Frame 160M/L
Output 11 kW (15 HP)
Number of Poles 4
Frequency 50 Hz
Rated speed 1470 rpm
Slip 2.00 %
Rated voltage 380/660 V
Rated current 21.9/12.6 A
L. R. Amperes 142/82.0 A
LRC 6.5
No load current 8.50/4.89 A
Rated torque 52.7 ft.lb
Locked rotor torque 200 %
Breakdown torque 250 %
Locked rotor time 23s (cold) 13s (hot)
Moment of inertia (J) 2.49 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 417 lb
Efficiency
50% 89.5
75% 90.2
100% 89.8
Power factor
50% 0.69
75% 0.79
100% 0.85
Electric Motors
Frame 160M/L
Output 11 kW (15 HP)
Number of Poles 4
Frequency 50 Hz
Rated speed 1475 rpm
Slip 1.67 %
Rated voltage 400/690 V
Rated current 21.2/12.3 A
L. R. Amperes 148/86.0 A
LRC 7.0
No load current 9.50/5.51 A
Rated torque 52.6 ft.lb
Locked rotor torque 229 %
Breakdown torque 280 %
Locked rotor time 21s (cold) 12s (hot)
Moment of inertia (J) 2.49 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 417 lb
Efficiency
50% 89.0
75% 90.2
100% 90.2
Power factor
50% 0.65
75% 0.76
100% 0.83
Electric Motors
Frame 160M/L
Output 11 kW (15 HP)
Number of Poles 4
Frequency 50 Hz
Rated speed 1476 rpm
Slip 1.60 %
Rated voltage 415 V
Rated current 20.9 A
L. R. Amperes 157 A
LRC 7.5
No load current 10.0 A
Rated torque 52.5 ft.lb
Locked rotor torque 250 %
Breakdown torque 300 %
Locked rotor time 21s (cold) 12s (hot)
Moment of inertia (J) 2.49 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 61.0 dB(A)
Approx. weight³ 417 lb
Efficiency
50% 88.5
75% 90.0
100% 90.2
Power factor
50% 0.61
75% 0.73
100% 0.81
Electric Motors
Frame 160M/L
Output 11 kW (15 HP)
Number of Poles 4
Frequency 60 Hz
Rated speed 1778 rpm
Slip 1.22 %
Rated voltage 460 V
Rated current 18.5 A
L. R. Amperes 152 A
LRC 8.2
No load current 8.50 A
Rated torque 43.6 ft.lb
Locked rotor torque 310 %
Breakdown torque 320 %
Locked rotor time 27s (cold) 15s (hot)
Moment of inertia (J) 2.49 sq.ft.lb
Design N
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle S1
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP56
Enclosure IC411 - TEFC
Mounting B3T
Rotation¹ Both (CW and CCW)
Noise level² 64.0 dB(A)
Approx. weight³ 417 lb
Efficiency
50% 88.5
75% 90.2
100% 91.0
Power factor
50% 0.62
75% 0.75
100% 0.82
Features
Frame Material Cast Iron
Impregnation Method Dip and Bake Polyester
Regreasing System At Drive end and Non-drive end
Space Heater Voltage 200 - 240 V
Main terminal box hole 2xM40x1,5
Terminal Block BMC - 6 pins
Shaft Locking Device Without
Shaft Material SAE 1040/45 Carbon Steel
Painting RAL 5009 205P (ISO 12944 - C4)
Grounding Lugs Double
Fan Cover material Cast Iron
Tropicalized Painting Without
Joints Seal Lumomoly
Fan material Aluminum
Bearing cap Yes- Bearing Cap
Bolt Material Carbon Steel
Winding thermal protection Thermistor - 2 wires 1 per phase 150°C
Balancing Method 1/2 Key
Drip Cover Without
Overload protector (phenolic) Without overload protector
Connection Cables Quantity 6
Downloads

You may also like

Recently viewed