WEG 12518XT3G444T W21 Explosion-proof Motor NEMA Premium Efficiency 125 HP 4P 444/5T 3Ph 460 V 60 Hz IC411 - TEFC - Foot-mounted

WEGSKU: 12518XT3G444T

GTIN : 7892304607633

MPN :

Dropship

Price:
Sale price$19,961.00

Description

WEG Explosion-proof motor was especially designed to operate in environments with the presence of explosive atmospheres. It has robust construction, a flame retention system with gaps between the parts carefully designed, accurate machining on the terminal box and screws with high mechanical strength. It meets the requirements of explosive atmospheres like Division I/Zone 1. Motors are certified for VFD service.

Standard NEMA MG-1
Frequency 60 Hz
Voltage 460 V
Number of poles 4
Degree of Protection IP55
Synchronous speed 1800 rpm
Output rating 125 HP
Mounting F-1
Flange Without
Terminal box¹ Left position
Enclosure IC411 - TEFC


Electric Motors
Frame 444/5T
Output 125 HP
Number of Poles 4
Frequency 60 Hz
Rated speed 1785 rpm
Slip 0.83 %
Rated voltage 460 V
Rated current 139 A
L. R. Amperes 945 A
LRC 6.8x(Code G)
No load current 45.0 A
Rated torque 368 ft.lb
Locked rotor torque 200 %
Breakdown torque 220 %
Locked rotor time 75s (cold) 42s (hot)
Moment of inertia (J) 57.2 sq.ft.lb
Design B
Insulation Class F
Service factor 1.15
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 76.0 dB(A)
Approx. weight³ 1969 lb
Efficiency
50% 94.3
75% 95.2
100% 95.4
Power factor
50% 0.75
75% 0.82
100% 0.85
Electric Motors
Frame 444/5T
Output 100 HP (75 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1485 rpm
Slip 1.00 %
Rated voltage 380 V
Rated current 142 A
L. R. Amperes 852 A
LRC 6.0x(Code G)
No load current 44.5 A
Rated torque 354 ft.lb
Locked rotor torque 190 %
Breakdown torque 210 %
Locked rotor time 84s (cold) 47s (hot)
Moment of inertia (J) 57.2 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 72.0 dB(A)
Approx. weight³ 1969 lb
Efficiency
50% 94.5
75% 94.5
100% 94.5
Power factor
50% 0.75
75% 0.83
100% 0.85
Electric Motors
Frame 444/5T
Output 100 HP (75 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1487 rpm
Slip 0.87 %
Rated voltage 400 V
Rated current 136 A
L. R. Amperes 952 A
LRC 7.0x(Code H)
No load current 47.2 A
Rated torque 353 ft.lb
Locked rotor torque 210 %
Breakdown torque 240 %
Locked rotor time 77s (cold) 43s (hot)
Moment of inertia (J) 57.2 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 72.0 dB(A)
Approx. weight³ 1969 lb
Efficiency
50% 94.5
75% 95.0
100% 94.5
Power factor
50% 0.73
75% 0.81
100% 0.84
Electric Motors
Frame 444/5T
Output 100 HP (75 kW)
Number of Poles 4
Frequency 50 Hz
Rated speed 1488 rpm
Slip 0.80 %
Rated voltage 415 V
Rated current 132 A
L. R. Amperes 977 A
LRC 7.4x(Code H)
No load current 49.3 A
Rated torque 353 ft.lb
Locked rotor torque 229 %
Breakdown torque 260 %
Locked rotor time 73s (cold) 41s (hot)
Moment of inertia (J) 57.2 sq.ft.lb
Design B
Insulation Class F
Service factor 1.00
Temperature rise 80 K
Duty Cycle Cont.(S1)
Starting Method Direct On Line
Ambient temperature -20°C to +40°C
Altitude 1000 m.a.s.l.
Degree of Protection IP55
Enclosure IC411 - TEFC
Mounting F-1
Rotation¹ Both (CW and CCW)
Noise level² 72.0 dB(A)
Approx. weight³ 1969 lb
Efficiency
50% 94.5
75% 95.0
100% 95.0
Power factor
50% 0.71
75% 0.80
100% 0.83
Features
Frame Material Cast Iron
Impregnation Method Constant Resin Flow
Regreasing System At Drive end and Non-drive end
Main terminal box hole 2xNPT 3"
Terminal Block Without
Shaft Locking Device Without
Drain Sinterized, Exd
Shaft Material SAE 4140 Carbon Steel
Painting RAL 5009 202P (ISO 12944 - C4)
Grounding Lugs Double
Fan Cover material Cast Iron
Tropicalized Painting Without
Fan material Aluminum
Bearing cap Yes- Bearing Cap
Bolt Material Carbon Steel
Winding thermal protection Thermostat - 2 wires 1 per phase 155°C
Drip Cover Without
Overload protector (phenolic) Without overload protector
Connection Cables Quantity 12
Downloads