Baldor VEM4104T 30HP, 1760RPM, 3PH, 60HZ, 286TC, 1056M, TEFC, F

BaldorSKU: VEM4104T

Dropship

Get it by Wed, Jan 29 - Mon, Feb 03

Price:
Sale price$5,129.37

Description

Specs
Catalog Number VEM4104T
Enclosure TEFC
Frame 286TC
Frame Material Iron
Frequency 60.00 Hz
Motor Letter Type Three Phase
Output @ Frequency 30.000 HP @ 60 HZ
Phase 3
Synchronous Speed @ Frequency 1800 RPM @ 60 HZ
Voltage @ Frequency 460.0 V @ 60 HZ 230.0 V @ 60 HZ
XP Class and Group None
XP Division Not Applicable
Agency Approvals NEMA_PREMIUM UR NEMA PREMIUM CSA EEV
Ambient Temperature 40 °C
Auxillary Box No Auxillary Box
Auxillary Box Lead Termination None
Base Indicator No Mounting
Bearing Grease Type Polyrex EM (-20F +300F)
Blower None
Current @ Voltage 76.000 A @ 230.0 V 78.000 A @ 208.0 V 38.000 A @ 460.0 V
Design Code A
Drip Cover No Drip Cover
Duty Rating CONT
Efficiency @ 100% Load 93.6 %
Electrically Isolated Bearing Not Electrically Isolated
Feedback Device NO FEEDBACK
High Voltage Full Load Amps 38.0 a
Front Face Code Standard
Front Shaft Indicator None
Heater Indicator No Heater
Insulation Class F
Inverter Code Inverter Ready
IP Rating NONE
KVA Code J
Lifting Lugs Standard Lifting Lugs
Locked Bearing Indicator Locked Bearing
Motor Lead Exit Ko Box
Motor Lead Termination Flying Leads
Motor Lead Quantity/Wire Size 9 @ 8 AWG
Motor Type 1056M
Mounting Arrangement F1
Number of Poles 4
Overall Length 27.76 IN
Power Factor 80
Product Family General Purpose
Pulley End Bearing Type Ball
Pulley Face Code C-Face
Pulley Shaft Indicator Standard
Rodent Screen None
Service Factor 1.15
Shaft Diameter 1.875 IN
Shaft Extension Location Pulley End
Shaft Ground Indicator No Shaft Grounding
Shaft Rotation Reversible
Shaft Slinger Indicator Shaft Slinger
Speed 1760 rpm
Speed Code Single Speed
Motor Standards NEMA
Starting Method Direct on line
Thermal Device - Bearing None
Thermal Device - Winding None
Vibration Sensor Indicator No Vibration Sensor
Winding Thermal 1 None
Winding Thermal 2 None
Drawings
Nameplate
CAT.NO. VEM4104T
SPEC. 10C153Y538G2
HP 30
R.P.M. 1760
VOLTS 230/460
AMPS 76/38
RATING 40C AMB-CONT
P.F. 80
USABLE AT 50Hz 30HP 190/380V 88/44A
Performance
Rated Load 50% 75% 100% 125% 150% S.F.
Power Factor 5.0 41.0 63.0 73.0 80.0 82.0 85.0 81.0
Efficiency 0.0 87.6 92.3 93.5 93.7 93.4 92.9 93.5
Speed (RPM) 1,799 1,792 1,788 1,782 1,776 1,770 1,762 1,773
Line Amps 17.90 19.80 24.30 30.70 37.60 45.60 55.20 42.40
Parts

You may also like

Recently viewed