Description
Specs
| Catalog Number | IR3507M |
|---|---|
| Enclosure | TEFC |
| Frame | 56 |
| Frame Material | Steel |
| Frequency | 60.00 Hz |
| Motor Letter Type | Cap Start, Induction Run |
| Output @ Frequency | .750 HP @ 60 HZ |
| Phase | 1 |
| Synchronous Speed @ Frequency | 1800 RPM @ 60 HZ |
| Voltage @ Frequency | 115.0 V @ 60 HZ 208.0 V @ 60 HZ 230.0 V @ 60 HZ |
| XP Class and Group | None |
| XP Division | Not Applicable |
| Agency Approvals | UR CSA |
| Ambient Temperature | 40 °C |
| Auxillary Box | No Auxillary Box |
| Auxillary Box Lead Termination | None |
| Base Indicator | Rigid |
| Bearing Grease Type | Polyrex EM (-20F +300F) |
| Blower | None |
| Current @ Voltage | 4.600 A @ 230.0 V 4.800 A @ 208.0 V 9.200 A @ 115.0 V |
| Design Code | N |
| Drip Cover | No Drip Cover |
| Duty Rating | CONT |
| Efficiency @ 100% Load | 70.0 % |
| Electrically Isolated Bearing | Not Electrically Isolated |
| Feedback Device | NO FEEDBACK |
| High Voltage Full Load Amps | 4.6 a |
| Front Face Code | Standard |
| Front Shaft Indicator | None |
| Heater Indicator | No Heater |
| Insulation Class | F |
| Inverter Code | Not Inverter |
| KVA Code | K |
| Lifting Lugs | No Lifting Lugs |
| Locked Bearing Indicator | No Locked Bearing |
| Motor Lead Exit | Ko Box |
| Motor Lead Termination | Flying Leads |
| Motor Lead Quantity/Wire Size | 6 @ 18 AWG |
| Motor Type | 3524L |
| Mounting Arrangement | F1 |
| Number of Poles | 4 |
| Overall Length | 13.23 IN |
| Power Factor | 76 |
| Product Family | General Purpose |
| Product Type | FARM DUTY |
| Pulley End Bearing Type | Ball |
| Pulley Face Code | Standard |
| Pulley Shaft Indicator | Standard |
| Rodent Screen | None |
| Service Factor | 1.00 |
| Shaft Diameter | 0.625 IN |
| Shaft Extension Location | Pulley End |
| Shaft Ground Indicator | No Shaft Grounding |
| Shaft Rotation | Reversible |
| Shaft Slinger Indicator | No Slinger |
| Speed | 1725 rpm |
| Speed Code | Single Speed |
| Motor Standards | NEMA |
| Starting Method | Direct on line |
| Thermal Device - Bearing | None |
| Thermal Device - Winding | None |
| Vibration Sensor Indicator | No Vibration Sensor |
| Winding Thermal 1 | Manual Thermal Overload |
| Winding Thermal 1 Location | KO |
| Winding Thermal 2 | None |
Drawings
Nameplate
| CAT.NO. | IR3507M |
|---|---|
| SPEC. | 35K634T918G1 |
| HP | .75 |
| VOLTS | 115/208-230 |
| AMP | 9.2/4.8-4.6 |
| RPM | 1725 |
| FRAME | 56 |
| SER.F. | 1.00 |
| NEMA-NOM-EFF | 70 |
| RATING | 40C AMB-CONT |
| DE | 6205 |
| ENCL | TEFC |
Performance
| Line-Line Res. @ 25° C | 0.905 Ohms A Ph / 1.82 Ohms B Ph |
|---|---|
| Start Configuration | DOL |
| Break-Down Torque | 5.3 LB-FT |
| Pull-Up Torque | 5 LB-FT |
| Locked-Rotor Torque | 7.7 LB-FT |
| Starting Current | 54 A |
| Rated Load | Rated Load | 0% | 25% | 50% | 75% | 100% | 125% | 150% | S.F. | |
|---|---|---|---|---|---|---|---|---|---|---|
| Power Factor | 19.0 | 42.0 | 58.0 | 72.0 | 78.0 | 83.0 | 84.0 | 0.0 | ||
| Efficiency | 0.0 | 54.0 | 67.7 | 72.9 | 74.2 | 73.8 | 71.8 | 0.0 | ||
| Speed (RPM) | 1,797 | 1,785 | 1,773 | 1,759 | 1,744 | 1,725 | 1,703 | 0 | ||
| Line Amps | 5.40 | 5.60 | 6.40 | 7.20 | 8.60 | 10.00 | 12.00 | 0.00 |
Parts
| EC1645A06SP | ELEC CAP, 645-774 MFD, 125V, 2.06D X 4. |
|---|---|
| 36GS1000SP | GASKET-CONDUIT BOX, .06 THICK #SV-330 LE |
| RM1014A01SP | BUTYL RUB.THRM COV. (MENA) |
| 35FH4005A32SP | IEC FH NO GRSR W/3 HOLES - PRIMED |
| 35FN3002A05SP | EXFN, PLASTIC, 6.376 OD, .638 ID |
| MN416A01 | TAG-INSTAL-MAINT no wire (2100bx)4/22 |