Description

Specs
Catalog Number CEWDM4117T
Enclosure TEFC
Frame 326TC
Frame Material Iron
Frequency 60.00 Hz
Motor Letter Type Three Phase
Output @ Frequency 30.000 HP @ 60 HZ
Phase 3
Synchronous Speed @ Frequency 1200 RPM @ 60 HZ
Voltage @ Frequency 460.0 V @ 60 HZ 230.0 V @ 60 HZ
XP Class and Group None
XP Division Not Applicable
Agency Approvals CSA EEV NEMA PREMIUM NEMA_PREMIUM UR
Ambient Temperature 40 °C
Auxillary Box No Auxillary Box
Auxillary Box Lead Termination None
Base Indicator Rigid
Bearing Grease Type Polyrex EM (-20F +300F)
Blower None
Current @ Voltage 78.000 A @ 230.0 V 39.000 A @ 460.0 V
Design Code A
Drip Cover No Drip Cover
Duty Rating CONT
Efficiency @ 100% Load 93.0 %
Electrically Isolated Bearing Not Electrically Isolated
Enclosure Modification Severe Duty Features
Feedback Device NO FEEDBACK
High Voltage Full Load Amps 39.0 a
Heater Indicator No Heater
Insulation Class F
Inverter Code Inverter Duty
IP Rating IP55
KVA Code H
Lifting Lugs Standard Lifting Lugs
Locked Bearing Indicator Locked Bearing
Max Speed 1800 rpm
Motor Lead Termination Flying Leads
Motor Type 1264M
Mounting Arrangement F1
Number of Poles 6
Overall Length 30.28 IN
Power Factor 78
Product Family Washdown Features
Pulley Face Code C-Face
Rodent Screen None
Service Factor 1.00
Shaft Diameter 2.125 IN
Shaft Ground Indicator No Shaft Grounding
Shaft Rotation Reversible
Speed 1180 rpm
Speed Code Single Speed
Motor Standards NEMA
Starting Method Direct on line
Thermal Device - Bearing None
Thermal Device - Winding None
Vibration Sensor Indicator No Vibration Sensor
Winding Thermal 1 None
Winding Thermal 2 None
Drawings
Nameplate
CAT.NO. CEWDM4117T
SPEC. 12-0000-0979
HP 30
VOLTS 230/460 20:1 CT/VT
AMP 78/39
RPM 1180
FRAME 326TC
SER.F. 1.00
NEMA-NOM-EFF 93
RATING 40C AMB-CONT
CC 010A
DE 6312
ENCL TEFC
BLANK 1.15SF ON SINEWAVE
Performance
Line-Line Res. @ 25° C 0.22799 Ohms A Ph / 0 Ohms B Ph
Temp. Rise @ Rated Load 56° C
Start Configuration DOL
Break-Down Torque 370 LB-FT
Pull-Up Torque 179 LB-FT
Locked-Rotor Torque 217 LB-FT
Starting Current 245 A
Rated Load Rated Load 0% 25% 50% 75% 100% 125% 150% S.F.
Power Factor 5.0 42.0 63.0 73.0 78.0 80.0 80.0 0.0
Efficiency 0.0 89.0 92.7 93.4 93.1 92.4 91.4 0.0
Speed (RPM) 1,199 1,196 1,192 1,188 1,183 1,178 1,172 0
Line Amps 17.20 19.20 24.10 31.00 38.70 47.50 57.30 0.00
Parts
MN416A01 TAG-INSTAL-MAINT no wire (2100bx)4/22
09FN3001B03SP EXTERNAL FAN, PLASTIC (COMES W/SCREW FRO

You may also like

Recently viewed