Description
Specs
| Catalog Number | CBXMN18242T |
|---|---|
| Enclosure | XPNV |
| Frame | 182TC |
| Frame Material | Steel |
| Frequency | 60.00 Hz |
| Motor Letter Type | Three Phase |
| Output @ Frequency | 2.000 HP @ 60 HZ |
| Phase | 3 |
| Synchronous Speed @ Frequency | 1800 RPM @ 60 HZ |
| Voltage @ Frequency | 230.0 V @ 60 HZ 460.0 V @ 60 HZ |
| XP Class and Group | CLI GP D; CLII GP F,G |
| XP Division | Division I |
| Agency Approvals | CSA EEV UL |
| Ambient Temperature | 40 °C |
| Auxillary Box | No Auxillary Box |
| Auxillary Box Lead Termination | None |
| Base Indicator | Rigid |
| Bearing Grease Type | Polyrex EM (-20F +300F) |
| Blower | None |
| Constant Torque Speed Range | 6 |
| Current @ Voltage | 5.400 A @ 230.0 V 5.000 A @ 190.0 V 2.700 A @ 460.0 V 2.500 A @ 380.0 V |
| Design Code | B |
| Drip Cover | No Drip Cover |
| Duty Rating | CONT |
| Efficiency @ 100% Load | 87.5 % |
| Electrically Isolated Bearing | Not Electrically Isolated |
| Feedback Device | NO FEEDBACK |
| High Voltage Full Load Amps | 2.5 a |
| Heater Indicator | No Heater |
| Insulation Class | F |
| Inverter Code | Inverter Duty |
| IP Rating | NONE |
| KVA Code | L |
| Lifting Lugs | No Lifting Lugs |
| Locked Bearing Indicator | Locked Bearing |
| Max Speed | 2700 rpm |
| Motor Lead Termination | Flying Leads |
| Motor Type | 3630M |
| Mounting Arrangement | F1 |
| Number of Poles | 4 |
| Overall Length | 23.24 IN |
| Power Factor | 79 |
| Product Family | General Purpose |
| Pulley Face Code | C-Face |
| Rodent Screen | None |
| Service Factor | 1.15 |
| Shaft Diameter | 1.125 IN |
| Shaft Ground Indicator | No Shaft Grounding |
| Shaft Rotation | Reversible |
| Speed | 1760 rpm |
| Speed Code | Single Speed |
| Motor Standards | NEMA |
| Starting Method | Direct on line |
| Thermal Device - Bearing | None |
| Thermal Device - Winding | Normally Closed Thermostat |
| Vibration Sensor Indicator | No Vibration Sensor |
| Winding Thermal 1 | None |
| Winding Thermal 2 | None |
| XP Temp Code | T3C |
Drawings
Nameplate
| SPEC. | 36-0000-0499 |
|---|---|
| CAT.NO. | CBXMN18242T |
| HP | 2//1.5 |
| VOLTS | 230/460//190/380 |
| AMPS | 5.4/2.7//5/2.5 |
| RPM | 1760//1470 |
| HZ | 60 |
| SER.F. | 1.15 |
| FRAME | 182TC |
Performance
| Full Load Torque | 0 LB-FT |
|---|---|
| No-Load Current | 0 A |
| Line-Line Res. @ 25° C | 1.3303 Ohms A Ph / 0 Ohms B Ph |
| Temp. Rise @ Rated Load | 50° C |
| Temp. Rise @ S.F. Load | 55° C |
| Start Configuration | DOL |
| Break-Down Torque | 24.3 LB-FT |
| Pull-Up Torque | 9.24 LB-FT |
| Locked-Rotor Torque | 17 LB-FT |
| Starting Current | 46.2 A |
| Rated Load | Rated Load | 0% | 25% | 50% | 75% | 100% | 125% | 150% | S.F. | |
|---|---|---|---|---|---|---|---|---|---|---|
| Power Factor | 10.0 | 38.0 | 58.0 | 69.0 | 77.0 | 79.0 | 82.0 | 78.0 | ||
| Efficiency | 0.0 | 77.4 | 85.6 | 87.2 | 87.3 | 87.9 | 85.9 | 87.7 | ||
| Speed (RPM) | 1,798 | 1,792 | 1,784 | 1,777 | 1,764 | 1,760 | 1,751 | 1,762 | ||
| Line Amps | 2.94 | 3.24 | 3.85 | 4.65 | 5.57 | 6.61 | 7.83 | 6.19 |
Parts
| MN416A01 | TAG-INSTAL-MAINT no wire (2100bx)4/22 |
|---|---|
| 35CB3001A02SP | EXPL PROOF CONDUIT BOX, 3/4"PIPE TAP LEA |
| 35CB3500A01SP | CONDUIT BOX LID, MACH |